Construction
Conductor Stranded Tinned Copper
Insulation Foam PE
Colour Pair 1: 1 x white, 1 x blue Pair 2: 1 x white, 1 x orange
Pair 3: 1 x white, 1 x black Pair 4: 1 x green
1st Screen 1 x AL-Mylar Wrap, overlapping ≥ 25 %
Drain Wire Stranded Tinned Copper
Braid Shield Tinned Copper ; coverage ≥ 85%
Sheath PVC/LSZH/LSZH ATARUV
Braid Armour (Optional) Galvanized Steel Wire Braid
Outer Sheath (Optional) LSZH / LSZH ATARUV
Pair 1P 2P 3P 4P
  Nom. Cable OD mm
TC/FPE/OS/TCWB/PVC 6.5 8.5 9.5 11.5
TC/FPE/OS/TCWB/LSZH 6.5 8.5 9.5 11.5
TC/FPE/OS/TCWB/LSZH ATARUV 6.5 8.5 9.5 11.5
TC/FPE/OS/TCWB/LSZH/SWB/LSZH 10.8 13.4 13.8 15.8
         
 

Application

  • For multi-dropped,medium-speed,serial data communication in electrically noisy industrial environments.Application includes industrial networks using RS-485/RS- 422/RS-232 transceivers, for Process Automation (chemicals, brewing, paper mills), factory automation (autos, metal fabrication), HVAC, security, motor control and motion control.Suitable for outdoor installation.

Flame Rating

  • IEC 60332 – 1
 
Electrical properties  
Conductor Resistance (at 20ºC)   ≤ 58 Ω/km  
Capacitance cond. to cond. Nom. 12.5 pF/ft  
Impedance Nom. 120 Ω  
Rated Voltage 300 V  
Mechanical properties  
Operating temperature -20°C to +70°C  
Bend Radius 10 x OD  
     
Ordering Information
RS-485  part numbers are made up using the table below.
The part number starts with 48 to denote that it is an EIA-485 cable.
The following number shows the number of pairing and the last 2 numbers signifies the AWG.

Example of an EIA-485 part number

48124LB 

The above example describes an RS-485 SWB cable with 1 pair, 24 AWG. Sheath type LSZH, SWB

 

RS- 485 PAIRING AWG SHEATH OUTER JACKET ADDITIVE  
48 X XX X X X  
 
1 - 1 Pair
2 - 2 Pair
4 - 4 Pair


22 -22 AWG

(nil) - PVC
L- LSZH

B - SWB
RTV- Anti-Rodent, Anti-Termite, UV Resistance  
 

Draka RS-485 24 AWG FPE

Serial Data Communication Cable

Construction
Conductor Stranded Tinned Copper
Insulation Foam PE
Colour Pair 1: 1 x white, 1 x blue Pair 2: 1 x white, 1 x orange
Pair 3: 1 x white, 1 x black Pair 4: 1 x green
1st Screen 1 x AL-Mylar Wrap, overlapping ≥ 25 %
Drain Wire Stranded Tinned Copper
Braid Shield Tinned Copper ; coverage ≥ 85%
Sheath PVC/LSZH/LSZH ATARUV
Braid Armour (Optional) Galvanized Steel Wire Braid
Outer Sheath (Optional) LSZH / LSZH ATARUV
Pair 1P 2P 3P 4P
Nom. Cable OD mm
TC/FPE/OS/TCWB/PVC 6.2 8.5 9.1 9.8
TC/FPE/OS/TCWB/LSZH 6.2 8.5 9.1 9.8
TC/FPE/OS/TCWB/LSZH ATARUV 6.2 8.5 9.1 9.8
TC/FPE/OS/TCWB/LSZH/SWB/LSZH 10.7 13.0 13.6 14.3

Application

  • For multi-dropped,medium-speed,serial data communication in electrically noisy industrial environments.Application includes industrial networks using RS-485/RS- 422/RS-232 transceivers, for Process Automation (chemicals, brewing, paper mills), factory automation (autos, metal fabrication), HVAC, security, motor control and motion control.Suitable for outdoor installation.

Flame Rating

  • IEC 60332 – 1
Electrical properties
Conductor Resistance (at 20ºC)   ≤ 89 Ω/km
Capacitance cond. to cond. Nom. 12.5 pF/ft
Impedance Nom. 120 Ω
Rated Voltage 300 V
Mechanical properties
Operating temperature -20°C to +70°C
Bend Radius 10 x OD
Ordering Information
RS-485  part numbers are made up using the table below.
The part number starts with 48 to denote that it is an EIA-485 cable.
The following number shows the number of pairing and the last 2 numbers signifies the AWG.

Example of an EIA-485 part number

48124LB 

The above example describes an RS-485 SWB cable with 1 pair, 24 AWG. Sheath type LSZH, SWB

RS- 485 PAIRING AWG SHEATH OUTER JACKET ADDITIVE
48 X XX X X X
1 - 1 Pair
2 - 2 Pair
4 - 4 Pair


24 -24 AWG

(nil) - PVC
L- LSZH

B - SWB
RTV- Anti-Rodent, Anti-Termite, UV Resistance

Li-2YC11Y 2 x 2 x 0.22 mm² FRNC

CanBus-Cable

Application

  • The following CanBus cable is suitable for transmission of CanBus signals according to DIN19245 and EN 50170
  • The following CanBus cable is suitable for transmission of CanBus signals according to ISO 11898 – 2
  • The cable is suited for fixed indoor and outdoor installation and under certain conditions also for mobile use.
  • The cable is halogen free,flame retardant and oil resistant. The sheath material is tested in Hydraulic oil.
  • ARAL VITAM 32, Mobil DTE 13 M, Gear oil ARAL DEGOL BG Plus 320 and Tribol 1710/320

Flame resistance

  • IEC 60332 – 1,IEC -60332-3,IEC 60754 – 1 /2
Construction
Conductor Stranded bare copper wire, diameter 7 x 0.20 mm            
ø 0.60 mm(cross section 0.22 mm²)
Insulation PE,
ø1.75± 0.05 mm
Wall Thickness 0.46mm
Colour code Pair 1: 1 x white, 1 x brown
Core identification Pair 2: 1 x yellow, 1 x green
Cable lay up 4 cores twisted to a star quad
ø 4.2 mm
Wrapping 1 x PET-foil, overlapping
ø 4.3 mm
Overall screen Tinned copper braid
ø 5.0 mm, Optical coverage ≥ 85%
Foil 1 x PET-foil under sheath
ø 5.1 mm
Sheath PUR Low Smoke Zero Halogen
ø 6.9 ± 0.2 mm
Sheath colour Black, RAL 9005
Outer Diameter Nom. 6.9 mm
Weight Nom. 70 kg/km
Tensile force N 165
Mechanical properties
Bending radius
– moving application- fixed application
≥ 10 x outer diameter of cable

≥ 5 x outer diameter of cable

Operating temperature – 40°C up to + 85°C
UV resistance acc. to IEC60068-2-5
Ozone resistance acc. to EN 60811-2-1, clause 8
Smoke density acc. to EN 50268-2, IEC61034-1 and 2
Corrosivity EN 50267-1 and 2, IEC 60754-1 and 2
Electrical properties at 20°C
Conductor resistance (at 20 ± 5 °C) ≥ 87 /km
Characteristic impedance at 1 MHz 120 Ω± 15%
Capacitance at 800 Hz (nominal) 41 nF/kmm
Insulation resistance (at 20 ± 5 °C and 500 V) ≥10 GΩxkm
Capacitance unbalance (pair to ground) 1.2 kV
Ordering Information
P/N Product Description P.U
1003018 CS2878600 CanBus, Li-2YC11Y 2 x 2 x 0.22 mm² FRNC 1000m/drum

Li-09YS(St)C11Y 2 x 0.35 mm² LSZH

CanBus-Cable

Construction
Conductor Stranded bare copper wire, diameter 7 x 0.26 mm                     
ø 0.78 mm
(cross section 0.35 mm²)
Insulation Foam-Skin PP,
ø 2.2 ± 0.1 mm
wall thickness 0.71 mm
Twisting 2 cores + 2 x PP-fillers twisted to the pair
ø 4.4 mm
Core identification 1x white, 1x green
Overall screen 1 x PET-Al-foil +
ø 4.6 mm
tinned stranded drain wires 19 x 0,15 mm
+ tinned copper braid
ø 5.2 mm
optical coverage ≥ 65%
Foil 1 x PET-foil under sheath
ø 5.3 mm
Sheath PUR Low Smoke Zero Halogen
ø 6.8 ± 0.2 mm
wall thickness 0.75 mm
Sheath colour Black, RAL 9005
Outer Diameter Nom. 6.8 mm
Weight Nom. 46.7 kg/km
Tensile force N 165
Mechanical properties
Bending radius during installation
– without load
– with load
> 5 x cable diameter;

> 10 x cable diameter

Operating temperature – 30°C up to + 70°C
Storage temperature -40°C up to 85°C
UV resistance of sheath material acc. to IEC60068-2-5
Ozone resistance acc. to EN 60811-2-1, clause 8
Smoke density acc. to EN 50268-2, IEC61034-1 and 2
Corrosivity acc. EN 50267-1 and 2, IEC 60754-1 and 2
Electrical properties at 20°C
Conductor resistance (at 20 ± 5 °C) ≥ 54.5Ω /km
Characteristic impedance at 1 MHz 120 Ω± 15%
Insulation resistance (at 20 ± 5 °C and 500 V) >10 GΩxkm
Operating voltage (50 Hz, rms) 60 V
Test voltage (AC, 1 min) Core/core and core/screen 1.2 kV

Application

  • The following CanBus cable is suitable for transmission of CanBus signals according to DIN19245 and EN 50170
  • The following CanBus cable is suitable for transmission of CanBus signals according to ISO 11898 – 2
  • The cable is suited for fixed indoor and outdoor installation and under certain conditions also for mobile use.
  • The cable is halogen free,flame retardant and oil resistant. The sheath material is tested in Hydraulic oil.
  • ARAL VITAM 32, Mobil DTE 13M, Gear oil ARAL DEGOL BG Plus 320 and Tribol 1710/320

Flame resistance

  • IEC 60332 – 1,IEC -61034-2,IEC 60754 – 1 /2

Ordering Information
P/N Product Description P.U
1003011 CS2875900 CanBus-Cable, Li-09YS(St)C11Y 2 x 0.35 mm² LSZH 1000m/drum

EIB – BUS, LSZH

EIB-Bus Cable

Symmetrical data cable for EIB-BUS Systems

Application

Bus cable for indoor installations in EIB
(European Installation Bus) systems. The
cable is suitable for installation in ducts, on
risers and under data floors. PE insulated
plain copper conductors. The cable has an
overall Al/PETP-foil screen and a tinned
copper drain wire. The overall sheath is
made of flame retardant LSZH. The pair is
colour coded for easy identification.

Fire Rating

  • IEC 60332-1
Construction
Conductor Copper wire, bare 0.5 mm2, ø 0.80 mm
Insulation PE, 1.6 mm ø
Core identification Pair 1: Red, Black, Pair 2: Yellow, White
Pair stranding 2 conductors to the pair
Cable lay up 1 or 2 pairs to the core
Wrapping 1 x PET foil
Overall shielding Laminated AL-foil + Tinned copper drain wire
Outer Sheath LSZH, Green RAL 6018
Mechanical properties
Operating temperature – 25°C up to + 70°C
Min. Installation temperature – 5°C up to + 60°C
Minimum bending radius (without load)  4 x D
Smoke density (only for LSFROH types) acc. to IEC 61034-2
Corrosivity of fire gases (only for LSZH types) acc. to IEC 60754-1/2
Electrical properties at 20°C
Max. Cond. Resistance DC (max.) 37.5 Ω/km
Ordering Information
P/N Product Description P.U
EIB2P0.8L-GN EIB BUS Cable, 2PR x 0.8mm BC Shielded LSZH Green 500m/drum